Escape route width FREE
Work out the width of fire escape routes from the number of people. Below the result you find the formula and the standard.
Formula, example and standard
1 module = 60 cm = 50 people · min exit 80 cm
Example with the starting values (Number of people: 100): Exit width: 120 cm (2 modules). Escape stairs: min 120 cm.
- Standard module 60 cm = 50 people (DM 3/8/2015, the Italian fire code, V.6).
- Single emergency exit: at least 80 cm.
- Escape stairs: 120 cm minimum for occupancy > 50 people.
Source: DM 3/8/2015 · Codice Prevenzione Incendi (Italian fire code) · vigilfuoco.it
Indicative pre-sizing: it does not replace a calculation signed by a licensed engineer.